Sign In | Join Free | My udpf.com
China Wuxi Fenigal Science & Technology Co., Ltd. logo
Wuxi Fenigal Science & Technology Co., Ltd.
Wuxi Fenigal Science & Technology Co., Ltd Manufacturer and Supplier for Industrial & Lighting Products
Verified Supplier

6 Years

Home > Automation Control Relays >

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A

Wuxi Fenigal Science & Technology Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A

Brand Name : Schneider Electric (TeSys)

Model Number : LRD (TeSys D)

Certification : CE,CCC,CB etc.

Place of Origin : China

MOQ : 1 unit

Price : USD15~USD20

Payment Terms : T/T, Western Union

Supply Ability : 5,000pcs/month

Delivery Time : 5-8 working days or bulk order negotiate

Packaging Details : Standard export carton

Setting current : 4~6A, 32~38A,

Electricity type : AC,AC/DC

Main circuit rating voltage : 600V,220V,380V,110V,24V

Number of pole : 3,4

Phase : 3,1Phase

Frequency : 50/60Hz

Product name : Ac Contactor CJX2N-D09,3 pole Ac Contactor

Rated current : 38A, 95A etc.

Standard : IEC60947,EN/IEC60947-4-1

Contact Now

Schneider Electric LRD10C, LED35C Thermal Overload Relay For Contactor Setting Current 4~6A, 30~38A, 400V IEC947-4-1

characteristic

• Manual/automatic reset • Pre-wired components • Independently mounted terminal block • Remote electrical reset • 45mm wide to 18.5Kw, 55mm wide from 15Kw to 30Kw, can be combined with Tesys D contactors • Terminal block: screw terminal block, Everlink wiring Terminal • Class 10 A

Advantage

Safe and effective thermal protection
The LRD thermal protection relay integrates manual/remote reset function, and the screw terminal and Everlink terminal block are easy to install. It provides reliable thermal protection to the 620A for a full range of domestic Tesys D contactors, and can be assembled into a compact motor with the contactor of 150A. Starter.

application

Industry, infrastructure, construction, etc.:
• Standard motor protection • Line protection • Protection: Motor overload, phase loss

main information

Product Series

TeSys

product name

TeSys LRD

product type

E type 3-pole thermal overload relay

Product short name

LRD

Relay application

Motor protection

The scope of products

LC1D09...D38

Relay setting range

4...6 A

Additional information

Control type

Red (Press) button: Stop (Make N/C contact action, does not affect N/O contact)
Blue (press) button: reset

Current setting range

3 A on 120 V AC-15 for signal circuit
0.22 A on 125 V DC-15 for signal circuit

Hot off towing level

Level 10A in accordance with IEC 60947-4-1

Trip threshold

1.14 ± 0.06 In in accordance with IEC 60947-4-1

Phase loss sensitivity

Two phases 1.3 Ir, the other phase is 0 in accordance with IEC 60947-4-1

Rated impulse withstand voltage [Uimp]

6 kV in accordance with IEC 60801-5

Conventional heating current [Ith]

5 A applicable signal loop

Installation method

Mounted directly under the contactor
Base plate installation
DIN rail mounting terminal block

Wiring ability

Control circuit: Bolt fastening 2 1...2.5 mm2 Cable selection: Cord without cable terminal
Control circuit: Bolt fastening 2 1...2.5 mm2 Cable selection: Corded cable terminal
Power circuit: Bolt tightening 1 1.5...10 mm2 Cable selection: Cord without cable terminal
Power circuit: Bolt fastening 1 1...4 mm2 Cable selection: Cord with cable terminal
Control circuit: Bolt tightening 1 1...2.5 mm2 Cable selection: Cord without cable terminal
Control circuit: Bolt tightening 1 1...2.5 mm2 Cable selection: Corded cable terminal
Control circuit: Spring terminal 1 1...2.5 mm2 Cable selection: Cord without cable terminal
Power circuit: Spring terminal 1 1.5...4 mm2 Cable selection: Cord without cable terminal
Control circuit: Bolt tightening 1 1...2.5 mm2 Cable selection: Hard wire without wire terminal
Control circuit: Bolt fastening 2 1...2.5 mm2 Cable selection: Hard wire without wire terminal
Control circuit: Spring terminal 1 1...2.5 mm2 Cable selection: Hard wire without wire terminal
Power circuit: Bolt fastening 1 1...6 mm2 Cable selection: Hard wire without cable terminal
Power circuit: Spring terminal 1 1.5...4 mm2 Cable selection: Hard wire without cable terminal

Tightening torque

Control circuit: 1.7 Nm Fastened by bolts
Power circuit: 1.7 Nm Fastened by bolts

width

45 mm

depth

70 mm

product weight

0.124 kg

surroundings

Standards compliant

GB 14048.4
IEC 60947-4-1

certified product

CCC
CE

IP protection level

IP20 complies with IEC 60529

Protective measures

TH conforms to IEC 60068

Ambient temperature

-20...60 °C without derating in accordance with IEC 60947-4-1
-40...70 °C with derating

Storage ambient temperature

-60...70 °C

Refractory and resistant to abnormal high temperatures

850 °C in accordance with IEC 60695-2-1

Flame retardant

V1 complies with UL 94

Shock and vibration resistance

Seismic performance: 6 gn, in accordance with IEC 60068-2-6
Impact resistance: 15 gn, , 11 ms in accordance with IEC 60068-2-7

Insulation performance

6 kV on 50 Hz in accordance with IEC 60255-5

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A


Product Tags:

home ac contactor

      

electrical control equipment

      
Best LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A wholesale

LRD10C LED35C AC Motor Contactor Thermal Overload Relay Contactor Setting Current 4~6A 30~38A Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Wuxi Fenigal Science & Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)